Picture of a Schneider Tesys D Contactor 3 Pole  (3 No) AC-3 <= 440V 12A 220V AC Coil

Schneider Tesys D Contactor 3 Pole (3 No) AC-3 <= 440V 12A 220V AC Coil

Schneider Electrics logo Alias LC1D12M7
Product Code 2500090485

Product Overview

Product Features

  • [Icw] rated short-time withstand current:105 A <= 40 °C 10 s power circuit,210 A <= 40 °C 1 s power circuit,30 A <= 40 °C 10 min power circuit,61 A <= 40 °C 1 min power circuit,100 A 1 s signalling circuit,120 A 500 ms signalling circuit,140 A 100 ms signalling circuit
  • [Ie] rated operational current:12 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit,25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
  • [Ith] conventional free air thermal current:25 A at <= 60 °C for power circuit,10 A at <= 60 °C for signalling circuit
  • [Ue] rated operational voltage:<= 690 V AC 25-400 Hz for power circuit,<= 300 V DC for power circuit
  • [Ui] rated insulation voltage:600 V for power circuit certifications CSA,600 V for power circuit certifications UL,690 V for power circuit conforming to IEC 60947-4-1,690 V for signalling circuit conforming to IEC 60947-1,600 V for signalling circuit certifications CSA,600 V for signalling circuit certifications UL
  • [Uimp] rated impulse withstand voltage:6 kV conforming to IEC 60947
  • associated fuse rating:25 A gG at <= 690 V coordination type 2 for power circuit,40 A gG at <= 690 V coordination type 1 for power circuit,10 A gG for signalling circuit conforming to IEC 60947-5-1
  • auxiliary contact composition:1 NO + 1 NC
  • average impedance:2.5 mOhm at 50 Hz - Ith 25 A for power circuit
  • contactor application:motor control,resistive load
  • control circuit type:AC 50/60 Hz
  • control circuit voltage:220 V AC 50/60 Hz
  • device short name:LC1D
  • electrical durability:2 Mcycles 12 A AC-3 at Ue <= 440 V,0.8 Mcycles 25 A AC-1 at Ue <= 440 V
  • Irms rated making capacity:250 A at 440 V for power circuit conforming to IEC 60947,140 A AC for signalling circuit conforming to IEC 60947-5-1,250 A DC for signalling circuit conforming to IEC 60947-5-1
  • mechanical durability:15 Mcycles
  • motor power hp:1 hp at 115 V AC 50/60 Hz for 1 phase motors,2 hp at 230/240 V AC 50/60 Hz for 1 phase motors,3 hp at 200/208 V AC 50/60 Hz for 3 phases motors,3 hp at 230/240 V AC 50/60 Hz for 3 phases motors,7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors,10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
  • motor power kW:3 kW at 220-230 V AC 50/60 Hz,7.5 kW at 500 V AC 50/60 Hz,7.5 kW at 660-690 V AC 50/60 Hz,5.5 kW at 380-400 V AC 50/60 Hz,5.5 kW at 415-440 V AC 50/60 Hz
  • mounting support:plate,rail
  • operating rate:3600 cyc/h at <= 60 °C
  • operating time:4-19 ms opening,12-22 ms closing
  • overvoltage category:III
  • pole contact composition:3 NO
  • poles description:3P
  • power dissipation per pole:0.36 W AC-3,1.56 W AC-1
  • product certifications:BV,CCC,CSA,DNV,GL,GOST,RINA,UL,LROS
  • product name:TeSys D
  • product or component type:contactor
  • protective cover:with
  • range:TeSys
  • rated breaking capacity:250 A at 440 V for power circuit conforming to IEC 60947
  • safety reliability level:B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1,B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
  • standards:EN 60947-4-1,EN 60947-5-1,IEC 60947-4-1,IEC 60947-5-1,UL 508,CSA C22.2 No 14
  • tightening torque:power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm,power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2,control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm,control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • utilisation category:AC-1,AC-3